NICE5000 User Manual 8 Troubleshooting
- 209 -
Fault
Code
Name Possible Causes Solution Level
Err31
Emergency
running
abnormal
1: Overspeed occurs
during inspection or
shaft auto-tuning.
2: The running speed
exceeds 1.15 times of
the maximum speed
(F0-03).
3: The speeds during
shorting motor stator
braking mode and
emergency running
exceed 1/2 of the rated
speed.
1: Decrease the inspection speed or
perform motor auto-tuning again.
2:
Check that the encoder is normal.
Set the motor nameplate
parameters correctly
Perform motor auto-tuning again.
3:
Check that the shorting PMSM
stator contactor function is
enabled.
Check that the EPS capacity is
proper.
Check that the emergency running
speed is set properly.
Err33
Elevator speed
abnormal
101: The detected
running speed during
normal-speed running
exceeds the limit.
102: The speed
exceeds the limit during
inspection or shaft auto-
tuning.
103: The speed exceeds
the limit in shorting
stator braking mode.
104: The speed
exceeds the limit during
emergency running.
105: The emergency
running time protection
function is enabled (set
in Bit8 of F6-45), and the
running time exceeds
50s, causing the timeout
fault.
101:
Check whether the encoder is
used properly.
Check the setting of motor
nameplate parameters. Perform
motor auto-tuning again.
102: Attempt to decrease the
inspection speed or perform motor
auto-tuning again.
103: Check whether the shorting
PMSM stator function is enabled.
104, 105:
Check whether the emergency
power capacity meets the
requirements.
Check whether the emergency
running speed is set properly.
5A
Err34 Logic fault
Logic of the MCB is
abnormal.
Contact the agent or Monarch.
5A