3 Mechanical and Electrical Installation NICE5000 User Manual
- 38 -
Cross-sectional Area of a Phase
Conductor (S)
Min. Cross-sectional Area of
Protective Conductor (Sp)
S ≤ 16 mm
2
S
16 mm
2
< S ≤ 35 mm
2
16 mm
2
35 mm
2
< S S/2
Description of Control Circuit Terminals
Table 3-2 Description of control circuit terminals
Mark Code Terminal Name Function Description
Terminal
Arrangement
CN1 X1 to X12
DI
Optocoupler isolation
Input voltage range: 10–30 VDC
Input impedance: 4.7 kΩ
Input current limit: 5 mA
Functions set in F5-01 to F5-20,
slow-down switch connected to a
terminal among X1 to X8
X5
X6
X7
X8
X9
X10
X1
X2
X3
X4
CN1
CN2
X13 to X20
X17
X18
X19
X20
M
AI
X13
X14
X15
X16
CN2
AI
AI
Input voltage range: -10 to 10 VDC
Used for the analog load cell device
M
CN3
+24V
24 VDC power
supply
24 VDC power supply for the MCB,
used for the input, output, and
communication circuits
M24
CN3
MCM
Mod1
Mod1
CAN1
CAN1
COM
Mod1+ Modbus
communication
terminal
HCB serial communication terminal
Mod1-
CAN1+
CANbus
communication
terminal
CTB CAN communication terminal
CAN1-
CN4
Y5-M5
Y6-M6
Relay output
Normally-open (NO), maximum
current and voltage rating: 5 A, 250
VAC
Function set in F5-36 and F5-37
CN4
Y5 M5 Y6
X31X30X29
M6
XCOM
X29,
X30,
X31-XCOM
DI
Safety circuit and door lock circuit
higher-voltage input terminals
Input voltage range: 95–125 VAC
Function set in F5-29 to F5-31