5 System Commissioning and Functions NICE5000 User Manual
- 94 -
Assume that there are two elevators in parallel mode. Elevator 1 stops at oor B1, oor 1,
oor 2, and oor 3, while elevator 2 stops at oor 1, oor 3, and oor 4. Now, you need to
set related parameters and HCB addresses according to the following table.
Table 5-6 Parameter setting and HCB addresses of two elevators
Elevator 1 Elevator 2
Number of elevators
in parallel/group mode
(Fd-00)
2 2
Elevator No. (Fd-01) 1 2
Actual oor
Physical
oor
HCB
address
HCB display HCB address HCB display
B1 1 1 FE-01 = 1101
1 2 2 FE-02 = 1901 2 FE-02 = 1901
2 3 3 FE-03 = 1902
Non-stop oor but
leveling plate required
FE-03 = 1902
3 4 4 FE-04 = 1903 4 FE-04 = 1903
4 5 5 FE-05 = 1904
Bottom oor
(F6-01)
1 2
Top oor (F6-00) 4 5
Service oor (F6-05) 65535 65531 (not stop at physical oor 3)