EasyManuals Logo

Moxa Technologies ioLogik E1200 Series User Manual

Moxa Technologies ioLogik E1200 Series
105 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #85 background imageLoading...
Page #85 background image
ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-10
1xxxx Read Only Coils (Function 2)
Reference
Address
Data Type
Description
10001
0x0000
1 bit
CH0 DI Value0=OFF1=ON (Read only)
10002
0x0001
1 bit
CH1 DI Value0=OFF1=ON (Read only)
10003
0x0002
1 bit
CH2 DI Value0=OFF1=ON (Read only)
10004
0x0003
1 bit
CH3 DI Value0=OFF1=ON (Read only)
10005
0x0004
1 bit
CH4 DI Value0=OFF1=ON (Read only)
10006
0x0005
1 bit
CH5 DI Value0=OFF1=ON (Read only)
10007
0x0006
1 bit
CH6 DI Value0=OFF1=ON (Read only)
10008
0x0007
1 bit
CH7 DI Value0=OFF1=ON (Read only)
10009
0x0008
1 bit
CH8 DI Value0=OFF1=ON (Read only)
10010
0x0009
1 bit
CH9 DI Value0=OFF1=ON (Read only)
10011
0x000A
1 bit
CH10 DI Value0=OFF1=ON (Read only)
10012
0x000B
1 bit
CH11 DI Value0=OFF1=ON (Read only)
10013
0x000C
1 bit
CH12 DI Value0=OFF1=ON (Read only)
10014
0x000D
1 bit
CH13 DI Value0=OFF1=ON (Read only)
10015
0x000E
1 bit
CH14 DI Value0=OFF1=ON (Read only)
10016
0x000F
1 bit
CH15 DI Value0=OFF1=ON (Read only)
14097
0x1000
1 bit
CH0 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14098
0x1001
1 bit
CH1 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14099
0x1002
1 bit
CH2 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14100
0x1003
1 bit
CH3 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14101
0x1004
1 bit
CH4 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14102
0x1005
1 bit
CH5 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14103
0x1006
1 bit
CH6 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14104
0x1007
1 bit
CH7 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14105
0x1008
1 bit
CH8 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14106
0x1009
1 bit
CH9 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14107
0x100A
1 bit
CH10 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14108
0x100B
1 bit
CH11 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14109
0x100C
1 bit
CH12 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14110
0x100D
1 bit
CH13 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14111
0x100E
1 bit
CH14 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14112
0x100F
1 bit
CH15 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14113
0x1010
1 bit
CH0 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14114
0x1011
1 bit
CH1 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14115
0x1012
1 bit
CH2 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14116
0x1013
1 bit
CH3 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14117
0x1014
1 bit
CH4 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14118
0x1015
1 bit
CH5 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14119
0x1016
1 bit
CH6 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14120
0x1017
1 bit
CH7 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14121
0x1018
1 bit
CH8 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14122
0x1019
1 bit
CH9 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14123
0x101A
1 bit
CH10 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14124
0x101B
1 bit
CH11 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14125
0x101C
1 bit
CH12 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14126
0x101D
1 bit
CH13 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14127
0x101E
1 bit
CH14 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14128
0x101F
1 bit
CH15 DO P2P Output Safe Status 0=Normal, 1=Safe Mode

Table of Contents

Other manuals for Moxa Technologies ioLogik E1200 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Moxa Technologies ioLogik E1200 Series and is the answer not in the manual?

Moxa Technologies ioLogik E1200 Series Specifications

General IconGeneral
BrandMoxa Technologies
ModelioLogik E1200 Series
CategoryNetwork Router
LanguageEnglish

Related product manuals