ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-14
Reference
Address
Data Type
Description
10006
0x0005
1 bit
CH5 DI Value, 0=OFF, 1=ON (Read only)
10007
0x0006
1 bit
CH6 DI Value, 0=OFF, 1=ON (Read only)
10008
0x0007
1 bit
CH7 DI Value, 0=OFF, 1=ON (Read only)
10009
0x0008
1 bit
CH8 DI Value, 0=OFF, 1=ON (Read only)
10010
0x0009
1 bit
CH9 DI Value, 0=OFF, 1=ON (Read only)
10011
0x0010
1 bit
CH10 DI Value, 0=OFF, 1=ON (Read only)
10012
0x0011
1 bit
CH11 DI Value, 0=OFF, 1=ON (Read only)
14097
0x1000
1 bit
CH0 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14098
0x1001
1 bit
CH1 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14099
0x1002
1 bit
CH2 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14100
0x1003
1 bit
CH3 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14101
0x1004
1 bit
CH4 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14102
0x1005
1 bit
CH5 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14103
0x1006
1 bit
CH6 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14104
0x1007
1 bit
CH7 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14113
0x1010
1 bit
CH0 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14114
0x1011
1 bit
CH1 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14115
0x1012
1 bit
CH2 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14116
0x1013
1 bit
CH3 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14117
0x1014
1 bit
CH4 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14118
0x1015
1 bit
CH5 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14119
0x1016
1 bit
CH6 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14120
0x1017
1 bit
CH7 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14129
0x1020
1 word
CH0 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
14130
0x1021
1 word
CH1 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
14131
0x1022
1 word
CH2 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
14132
0x1023
1 word
CH3 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
14133
0x1024
1 word
CH4 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
14134
0x1025
1 word
CH5 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
14135
0x1026
1 word
CH6 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
14136
0x1027
1 word
CH7 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero

Table of Contents

Other manuals for Moxa Technologies ioLogik E1200 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Moxa Technologies ioLogik E1200 Series and is the answer not in the manual?

Moxa Technologies ioLogik E1200 Series Specifications

General IconGeneral
BrandMoxa Technologies
ModelioLogik E1200 Series
CategoryNetwork Router
LanguageEnglish

Related product manuals