ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-11
ioLogik E1240 Modbus Address and Register
Map
I/O
Parameter Name Description Start
Address
(decimal)
Point
Type
Start
Register
(decimal)
Length Access Type
AI_burnoutValue high/low word 0040 03:HOLDI
NG
REGISTER
40041 16 R/W 2 words
AI_mode 0: 0-10 V
1: 4-20mA
2: 0-20mA
4: 4-20mA
burnout
0024 03:HOLDI
NG
REGISTER
40025 8 R/W word
AI_rawValue 0000 04:INPUT
REGISTER
30001 8 R word
AI_rawValueMax 0032 04:INPUT
REGISTER
30033 8 R word
AI_rawValueMin 0024 04:INPUT
REGISTER
30025 8 R word
AI_resetMaxValue 1: reset max.
value
4153 01:COIL
STATUS
04154 8 R/W bit
AI_resetMinValue 1: reset min.
value
4145 01:COIL
STATUS
04146 8 R/W bit
AI_scaledValue high/low word 0008 04:INPUT
REGISTER
30009 16 R 2 words
AI_scaledValueMax high/low word 0125 04:INPUT
REGISTER
30126 16 R 2 words
AI_scaledValueMin high/low word 0109 04:INPUT
REGISTER
30110 16 R 2 words
AI_status 0: normal,
1: burnout,
2: over range,
3: under range
0060 04:INPUT
REGISTER
30061 8 R word
System
Parameter Name Description Start
Address
(decimal)
Point
Type
Start
Register
(decimal)
Length Access Type
deviceName Each byte
represents
ASCII code of
each character
5040 04:INPUT
REGISTER
35041 30 R word
deviceUpTime unit: sec(s) 5020 04:INPUT
REGISTER
35021 2 R word
firmwareVersion e.g. V1.2.3 ->
1st byte: 1,
2nd byte: 2,
3rd byte: 3
5029 04:INPUT
REGISTER
35030 2 R word
firmwareBuildDate e.g.
Build16051718
--> 16051718
5031 04:INPUT
REGISTER
35032 2 R word

Table of Contents

Other manuals for Moxa Technologies ioLogik E1212

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Moxa Technologies ioLogik E1212 and is the answer not in the manual?

Moxa Technologies ioLogik E1212 Specifications

General IconGeneral
Cable typeAWG
Module typeDigital
Channel type-
Signal directionInput/output
Power consumption130 mA
Dimensions (WxDxH)27.8 x 84 x 124 mm
Output current range0 - 0.2 A
Ethernet LAN (RJ-45) ports2
Supported network protocolsModbus/TCP, TCP/IP, UDP, DHCP, Bootp, HTTP
Isolation3 kV
Channels quantity16 channels