Manual# I27028 6-17 Rev. 2 – 11/22/2017
6.18 CHECKING THE FLAME ROD
1. Be sure that the rod is securely mounted. If the outside of the rod is corroded,
gently clean it using fine (#0000) steel wool. The rod should be replaced once a
year.
2. Check the wiring and replace it if it is dried or cracked.
6.19 CHECKING THE SPARK PLUG
1. Remove the plug and check the gap. This should be 7/64 (0.10) inch.
2. Check the wiring and replace it if it is dried or cracked.
6.20 STORAGE AND LONG-TERM SHUT-DOWN
Turn off all energy inputs to the machine. Turn off all electrical power and the gas
supply.
The desiccant in the HoneyCombe® wheel will continue to absorb some moisture after the
dehumidifier is shut down. If the wheel is allowed to absorb too much moisture over a period
of time, the wheel may not be able to perform normally when the unit is turned on again.
Seal the dehumidifier to prevent the open air from reaching the HoneyCombe® wheel. This
can be done by fitting moisture barriers over the openings in the unit:
• Process inlet
• Process outlet
• Reactivation inlet
• Reactivation outlet
To make the moisture barriers, use strong plastic sheeting sealed with duct tape.