Munters Corporation - Dehumidification Division
Flow Data Sheet Rental Units
R-5000, R-10000, R-15000 Series
I20694
Rev 1
1/14/15
AMcD
Note: pressures across the wheel will vary (+/- 0.2” wc) depending on the inlet conditions
Process Inlet Conditions
(Same React Inlet)
Process Outlet Conditions
R-5000 R-10000 R-15000
80°F at 92 gr/lb
123°F at 43.4 gr/lb
126°F at 40.5 gr/lb
119°F at 49 gr/lb
55°F at 51.5 gr/lb
95°F at 8.9 gr/lb
97°F at 8.0 gr/lb
89°F at 15 gr/lb
95°F at 120 gr/lb
139°F at 71gr/lb
137°F at 73 gr/lb
129°F at 81 gr/lb
73°F at 115 gr/lb
117°F at 63gr/lb
121°F at 60 gr/lb
115°F at 66 gr/lb
60°F at Saturation 77gr/lb
102°F at 29gr/lb
106°F at 27 gr/lb
90°F at 32 gr/lb
Duct
Connections
React/Process
Connections
Electric React
(Generator Size)
Gas BTU/hr
Capacity
(Gas Connection*)
Full Load Amps
@460v/3/60
R-5000
18” or 20”
1 x react in/out
1 x process
in/out
84kW
(100kW)(125kVA)
300,000
(½” NPT)
132
R-10000
18” or 20”
1 x react in/out
2 x process
in/out
180kW
(225kW)(250kVA)
750,000
(1” NPT)
282
R-15000
18” or 20”
2 x react in
1 x react out
3 x process
in/out
252kW
(252kW) (280kVA)
1,000,000
(1” NPT)
340 - Elec. React
70 - Gas React
- Minimum Gas Pressure = 15” wc; Maximum Gas Pressure = 5 psi
- Propane or Natural Gas Compatible (simple regulator adjustment required)
Process Inlet
R05 – 5,000 scfm
R10 – 10,000 scfm
R15 -- 15,000 scfm
React Heat
30% Filter
Process Fan
React Fan
Metal Mesh Filter
Dehumidifier
Wheel
Expected
Performance
Conditions
React Outlet Temp
120°F (R05/R10)
130°F (R15)
Process Outlet
External static
pressure = 5” wc
Process*
R05 =2.2”
R10 =2.4”
R15 =2.6”
React*
R05 =2.1”
R10 =2.1”
R15 =2.8“
React Inlet
R05 – 1,400 scfm
R10 – 2,800 scfm
R15 – 3,750 scfm
Utility