© Munters AB, 2020 161
o
Co2 Shutoff Differential: (ppm): When CO2 levels are below the target level by this
amount, all CO2 treatment stops. Range: 0 to 500 ppm
o
High Co2 Alarm threshold (ppm): TRIO sends an alarm when the CO2 level rises above
this level. Range: 0 to 5000 ppm
o
NH3 Shutoff Differential: (ppm): When ammonia levels are below the target level by this
amount, all ammonia treatment stop. Range:0 ppm to 10 ppm
o
High NH3 Alarm threshold (ppm): TRIO sends an alarm when the ammonia level rises
above this level. Range: 0 to 100 ppm