© Munters AB, 2020 68
7.7 Inlets, Tunnel Doors, Outlets
•
Defining the Inlets/Tunnel Doors
•
Defining the Outlet
7.7.1 D
EFINING THE
I
NLETS
/T
UNNEL
D
OORS
Define up to four relays or analog output ports as inlets or tunnel doors (each device
requires two relays or one analogue port) (refer to Mapping Devices, page 50).
•
Define:
o
Normal State
o
Position: Define how the inlet opening is controlled:
By time
Potentiometer
o
Auto Calib.: Enable automatic calibration..
o
Power up calibration: Enable this parameter to calibrate inlets each time that TRIO is
turned on.
o
Open/Close Time: Enter the amount of time required to fully open or fully close the inlet.
These parameters are only enabled when Position/By Time is selected.