© Munters AB, 2020 113
o
Cold Max. Level: When the outside temperature reaches the Dynamic Maximum Cold
Outside Temperature, Minimum Ventilation will not go above this level.
o
Warm Max. Level: When the outside temperature reaches the Dynamic Maximum
Warm Outside Temperature, Minimum Ventilation will not go above this level.
11.2.2 V
ENTILATION BY
W
EIGHT
•
How Does Ventilation by Weight Work
•
Defining the Ventilation By Weight Parameters
11.2.2.1 How Does Ventilation by Weight Work
Ventilation by Weight provides air based on the number of birds in the house, their projected weight, and
the outside temperature. After calculating how much air is required based on these factors, TRIO
determines the required ventilation level to supply the air. Anytime that one of the factors changes, TRIO
recalculates the ventilation (to prevent changing the ventilation too frequently any change must be larger
than a user-defined amount).
•
When using cycle fans, each level has minimum and maximum on times, which determine the
minimum and maximum CFM. If the ventilation doesn't provide enough air for the birds (based on
their numbers and weight) TRIO sends an alarm. You will need to redefine the minimum level.
•
When using variable speed fans, the defined percentages determine the minimum and maximum
CFM. However, if a variable fan is set to run in a cycle, the cycle time determines the fan
operation, not the user-defined fan speed.
11.2.2.2 Defining the Ventilation By Weight Parameters
1. Go to System > Control Strategy > Ventilation .
2. Under Minimum / Maximum Ventilation, enable Min Ventilation By Weight.
3. Go to Climate > Min/Max Ventilation.