PROFINET IO
User manual 57106_hdb_en_13 76 / 94
Determination of FMM Slot 1: The module of slot
Nominal
= 1 is located in the actual configuration
on slot
Actual
= 2 FMM = 2
Slot 2: The module of slot
Nominal
= 2 is located in the actual configuration
on slot
Actual
= 1 FMM = 1
Slot 3: The module of slot
Nominal
= 3 is located in the actual configuration
on slot
Actual
= 3 FMM = 3
Slot 4: The module of slot
Nominal
= 4 is located in the actual configuration
on slot
Actual
= 5 FMM = 5
Slot 5: The module of slot
Nominal
= 5 is located in the actual configuration
on slot
Actual
= 6 FMM = 6
Slot 6: The module of slot
Nominal
= 6 is located in the actual configuration
on slot
Actual
= 4 FMM = 4
Legend
Variant 2 Swapped slots and modules are absent
Determination of FMM Slot 1: The module of slot
Nominal
= 1 is located in the actual configuration
on slot
Actual
= 1 FMM = 1
Slot 2: The module of slot
Nominal
2 is not available in the actual configura-
tion FMM = 255
Slot 3: The module of slot
Nominal
= 3 is located in the actual configuration
on slot
Actual
= 2 FMM = 2
Slot 4: The module of slot
Nominal
= 4 is located in the actual configuration
on slot
Actual
= 3 FMM = 3
Slot 5: The module of slot
Nominal
= 5 is located in the actual configuration
on slot
Actual
= 4 FMM = 4
Slot 6: The module of slot
Nominal
6 is not available in the actual configura-
tion FMM = 255
Data record 0x7F
Mapping 21356400...0
Slot
Nominal
The FMM configuration always refers to the port (slot) of the nominal
configuration.
Module
Nominal
Module on the port of the nominal configuration.
Slot
Actual
Port of the actual configuration.
Module
Actual
Module on the port of the actual configuration.
FMM For variant 1, FMM corresponds to the value of slot
Actual
i.e., the slot
of the actual configuration on which the module of the nominal con-
figuration is located.
FMM must be adapted during the configuration of the hardware vari-
ant.
(1): Nominal configuration
(2): Actual configuration
Slot
Nominal
Module
Nom-
inal
Slot
Actual
Module
Actu-
al
FMM
1DI1DI1
2 DO - DIO 255
3DIO2AI2
4AI3AO 3
5AO4 - 4
6 CP - - 255
1
2
PN
Slot
PN
DI
1
234
56
DI
DO DIO
DIO
AI
AI
AO
AO
CP
X
X
Data record 0x7F
Mapping 1 255 2 3 4 255 0 0 ... 0

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Murr Elektronik CUBE20S PROFINET IO and is the answer not in the manual?

Murr Elektronik CUBE20S PROFINET IO Specifications

General IconGeneral
BrandMurr Elektronik
ModelCUBE20S PROFINET IO
CategoryControl Unit
LanguageEnglish

Related product manuals