EasyManua.ls Logo

Murr Elektronik IMPACT67 Series - Data Storage Mode

Murr Elektronik IMPACT67 Series
145 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Description
User manual 55170_hdb_en_13 21 / 145
3.5.1 Data storage mode
NOTE
The data storage mode is only available for devices that comply with IO-Link
specification V1.1 and higher.
The data storage mode offers scope for replacing IO-Link devices without
reconfiguration.
The IO-Link master or the IO-Link device saves the set device parameters
of the previous configuration.
In data storage mode, the parameter data storage facilities on IO-Link
master and IO-Link device are synchronized.
Following replacement of a device, the master writes the saved device pa-
rameters to the new device whenever the data storage mode is enabled in
the IO-Link master. The application can be started without reconfiguration.
Following replacement of an IO-Link master, the device writes the saved
device parameters to the new master whenever the "Save & Restore" data
storage mode is enabled in the IO-Link master. The application can be
started without reconfiguration.

Table of Contents

Related product manuals