Technical Data
User manual 55170_hdb_en_13 30 / 145
Art.-No. 55151, 55152,
55171, 55172
4.2 Environmental characteristics
IO-Link
IO-Link devices operating voltage 24 V
IO-Link devices voltage range 20 ... 30 V
Specification V 1.1.2
Transfer rate Com 1 / Com 2 / Com 3
Transfer rate recognition Automatic
Input characteristic EN61131-2, Type 1
Climatic
Operating temperature -25 °C ... +55 °C
Storage temperature -25 °C ... +70 °C
provide acclimatization
for commissioning
Transport temperature -25 °C ... +70 °C
provide acclimatization
for commissioning
Relative humidity ≤95 %
Installation hight Above sea level ≤2 000 m
Mechanical
Oscillation test EN 60068 Part 2-6 10 ... 150 Hz,
Oscillation angle
0.35 mm, 5 g
Shock test EN 60068 Part 2-27 15 g, duration 11 ms
Electrical safety
Protection degree EN 60529 IP67
Protection class Using a SELV- or PELV- power supply III
Pollution degree 2
EMC-inteference
Radiated inteference E-field enclosure EN 55016-2-3 Conform
Radiated inteference voltage EN 55016-1-2 Conform
EMC-immunity
Electrostatic discharge (ESD) EN 61000-4-2 Conform
Electromagnetic RF-fields EN 61000-4-3 Conform
Fast transient burst EN 61000-4-4 Conform
Surge AC EN 61000-4-5 Conform
Conducted RF-fields EN 61000-4-6 Conform
Magnetic field 50/60 Hz EN 61000-4-8 Conform
Voltage dips EN 61000-4-11 Conform