12 of 35
Opus Control Wiring and Programming Installaon Manual www.NabcoEntrances.com
P/N C-00139 Rev 3-9-18
Movement Setting
Parameter Range Default Description
Open Timer 0-10, 12, 15, 20, 25, 30 2 Amount of Hold Open me aer deacvaon in seconds
Reaction Power 0 - 7 3 Determines how fast the door reacts to a reacvaon when closing
Open Recycle Sens 0 - 7 3 Determines how hard the door will push against an obstrucon
during opening
Close Recycle Sens 0 - 7 3
►
►
Aer Open Recycle Slow Open, Stop Slow Open Determines what happens aer a recycle during Opening cycle.
Close Recycle
Reopen
Yes Yes Determines what happens aer a recycle while closing cycle.
No
SECTION 9.3: Oponal Sengs
Optional Setting
Parameter Range Default Description
Hold Close Force 0 - 3 0 0 OFF
3 Strongest Hold Close force
Power Close Range
No Power
Close
Closing assisted by Motor to ght wind or stack pressure
Latch and Back
Manual Open Function No Acon No Acon Does nothing
Push and Go P & G Enables push and go
Stop and Close S & C Door pauses at open angle then closes
Open Assist
►
►
►
►
Manual Open Sensitivity 0 - 3 1 Angle/force to acvate Push and Go
Manual Open Timer
0-10, 12, 15, 20, 25, 30
4 Hold Open me for Manual Opening
BCHK Lockout Angle 0 - 9
A
0
►
► Range is from 0° to 30°
►
0 Narrow
A Wide
LCHK Lockout Angle 0 - 9
A
0
►
► Range is from 0° to 30°
►
0 Narrow
A Wide