ZONE DELAY TYPES
Only one option per zone can be
selected. For example; a zone cannot
be instant and delayed at the same.
ZONES 1–8 (D8 & D16) ZONES 916 (D16)
Option No. Description
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
P39E DOUBLE TRIGGER zones
P40E INSTANT zones ON ON ON ON ON ON ON ON ON ON ON ON ON ON
P41E ENTRY DELAY 1 zones ON
P42E HANDOVER zones ON
P43E ENTRY DELAY 2 zones
P44E LOCKOUT zones (Reset O/P) ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON
P45E AREA 1 zones ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON
P46E AREA 2 zones
P51E HOME zones
P52E 24HR zones
P53E DAY zones
DOUBLE TRIGGER ZONES
Zones programmed to Double Trigger will recognise an alarm condition if:



PROGRAMMING SEQUENCE:
P39E [Zone No]E toggles the options ON and OFF
[Zone No] OFF: The zone is not a Double Trigger zone
[Zone No] ON: The zone is a Double Trigger zone
P39E
PROGRAM MODE LEVEL
Installer mode or NessComms.
FACTORY DEFAULT
All OFF: No Double Trigger zones.
NOTES

unwanted alarms from zones in harsh
environments such as sheds and
garages.
0E will turn all selections OFF.
MEMORY E will turn all selections ON.
INSTANT ZONES
Instant Zones operate only in the Armed state. When Armed at the expiry of exit time,
Instant Zones will activate assigned outputs immediately when triggered.
PROGRAMMING SEQUENCE:
P40E [Zone No]E turns the options ON
[Zone No] ON: The zone is an Instant Zone
To deselect the option, select a different zone type in the DELAY GROUP.
P40E
PROGRAM MODE LEVEL
Installer mode or NessComms.
FACTORY DEFAULT
D8, 3E–8E ON: Zones 3–8 are Instant.
D16, 3E–16E ON: Zones 3–16 are
Instant.
NOTES

is automatically deselected from any other
zone type in the DELAY GROUP.
ENTRY DELAY1 ZONES
Entry Delay1 zones operate only in the Armed state. When Armed, at the expiry of exit
time these zones will activate the Entry Delay Timer1 (P26E) when they are triggered.
If the panel is not disarmed before the expiry of the Entry Delay Timer1, the alarm
outputs will be activated.
PROGRAMMING SEQUENCE:
P41E [Zone No]E turns the options ON
[Zone No] ON: The zone is an Entry Delay1 zone
To deselect the option, select a different zone type in the DELAY GROUP.
P41E
PROGRAM MODE LEVEL
Installer mode or NessComms.
FACTORY DEFAULT
1E ON: Zone 1 has Entry Delay1.
NOTES
 
Entry Delay as a reminder to disarm the
panel. Entry beeps can be disabled by
program option P60E 1E.

is automatically deselected from any other
zone type in the DELAY GROUP.
18
Ness D8x / D16x Control Panel – Installation Manual
PROGRAMMING