Connect to READER header
on the panel main board.
Blu
Brn
Grn
Wht
Red
Blk
1
2
3
Optional Reader Interface board.
Part No. 106-012
Blu
Brn
Grn
Wht
Red
Blk
Violet
101-014
Ultraprox
Weigand
Reader
WIRING A SINGLE READER
P301E 1E is OFF (Reader addresses not used)
Connect only 1 reader.
In this mode the panel is compatible with the 101-091 Ness
IDTeck Fingerprint Reader or the 101-014 Ness Ultraprox
Weigand Reader.
WIRING MULTIPLE READERS
P301E 1E is ON (Use Reader addresses)
When multiple readers are used, the panel needs to
identify the individual readers.
The 101-014 Ness Ultraprox Weigand Readers can be
addressed as Reader 1, 2 or 3 by connecting the Violet
wire to an appropriate terminal.
If using multiple Weigand readers, they must be either ALL
addressable or ALL non-addressable.
That is, use either three Ness 101-014 addressable Weigand
readers or three generic Weigand readers.
Recommended cable is twisted 3 pair
shielded cable with only one end of the
shield connected to ground.
For cable runs exceeding 75m use the Ness
Weigand data repeater.
REQUEST TO EXIT (REX) USING A KEYPAD CODE
Codes selected for Code Only Arming can be used as REX codes for access control functions. That is, the code can
operate an output instead of arming/disarming the panel.
There are two conditions needed to make the code operate as a REX code - It is assigned to CODE ONLY ARM and it
is not assigned to either Area 1 or Area 2.
The first digit of the user code determines which AUX output is operated by the REX code. That is, a REX code in the
format 1xxx operates AUX1, 2xxx operates AUX2 and 3xxx operates AUX3.
Notes:
1. Reader 1 can also use codes starting with 4-9 if only one exit point is used.
2. Set P318E, P328E, P338E options to select appropriate AUX outputs.
3. Set corresponding P121E, P122E, P123E, P124E options to 8E.
Setup Example:
Operation Example:
78
ACCESS CONTROL
Ness D8x / D16x Control Panel – Installation Manual