REPORT ZONE ALARMS
This option selects which zone inputs will send Alarm reports to the Central Station.
PROGRAMMING SEQUENCE:
P74E [Zone No]E toggles the option ON and OFF
[Zone No]E OFF: Alarm reporting disabled for that zone
[Zone No]E ON: Alarm reporting enabled for that zone
P74E
PROGRAM MODE LEVEL
Installer mode or NessComms.
FACTORY DEFAULT
All zones report Alarms.
NOTES

MEMORY E will turn all selections ON.
REPORT ZONE RESTORALS
This option selects which zone inputs will send Restoral reports to the Central Station.
Only zones that have previously sent an Alarm will send a Restoral.
PROGRAMMING SEQUENCE:
P76E [Zone No]E toggles the option ON and OFF
[Zone No]E OFF: Restoral reporting disabled for that zone
[Zone No]E ON: Restoral reporting enabled for that zone
P76E
PROGRAM MODE LEVEL
Installer mode or NessComms.
FACTORY DEFAULT
All zones report Restorals.
NOTES
0E will turn all selections OFF
MEMORY E will turn all selections ON
RELATED OPTIONS
P82E 1E Send Restoral immediately.
P82E 2E Send Restoral after siren time.

seal.
P82E 4E Send Restoral on Disarm
always.
REPORT MULTIPLE ZONE ALARMS
Zones selected for Multiple Zone Alarms will report each time the zone alarms and
without a restore being sent. The number of reports is a maximum of 15. The number
of alarms sent for each Multiple Zone Alarm can be reduced to 3 by using the swinger
shutdown option P89E 4E.
Zones not selected report only once, until reset by an opening or a valid code.
PROGRAMMING SEQUENCE:
P78E [Zone No]E toggles the option ON and OFF
[Zone No]E OFF: Multiple Zone Alarms disabled for that zone
[Zone No]E ON: Multiple Zone Alarms enabled for that zone
P78E
PROGRAM MODE LEVEL
Installer mode or NessComms.
FACTORY DEFAULT
No zones report Multiple Alarms.
NOTES

Alarm will send a Restoral.
0E will turn all selections OFF
MEMORY E will turn all selections ON
RELATED OPTIONS
P89E 4E Swinger shutdown.
ACCOUNT NO.2 ZONES
Zones selected to be Account No.2 zones will report their Alarms, Restorals and
Excludes on Client code 2.
PROGRAMMING SEQUENCE:
P79E [Zone No]E toggles the option ON and OFF
P79E
PROGRAM MODE LEVEL
Installer mode or NessComms.
FACTORY DEFAULT
none
ZONES 1–8 (D8 & D16) ZONES 916 (D16)
Option No. Description
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
P74E REPORT ZONE ALARMS
ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON
P76E REPORT ZONE RESTORALS
ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON
P78E MULTIPLE ZONE ALARMS
P79E ACCOUNT NUMBER 2 ZONES
40
Ness D8x / D16x Control Panel – Installation Manual
PROGRAMMING

Table of Contents

Other manuals for Ness D8X

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ness D8X and is the answer not in the manual?

Ness D8X Specifications

General IconGeneral
BrandNess
ModelD8X
CategoryControl Panel
LanguageEnglish

Related product manuals