CONTACT ID + AUDIBLE VOICE FORMAT
For simultaneous Central Station and Audible Monitoring.
The alarm message will be sent to the Central Station on the Primary telephone
number and then in audible VOICE format to the Follow Me telephone number, (P00E).
PROGRAMMING SEQUENCE:
P86E 6E turns the option ON
ON: Contact ID + Audible VOICE format enabled
P86E 6E
PROGRAM MODE LEVEL
Installer mode or NessComms.
FACTORY DEFAULT
OFF.
AUDIBLE VOICE FORMAT
For Audible Monitoring to any telephone or mobile phone. Zone alarms are sent in
Audible VOICE format. (Except D16x C-Bus model).
The message is repeated for 45 seconds or until kissed-off by the receiving telephone.
PROGRAMMING SEQUENCE:
P86E 4E turns the option ON
ON: Audible VOICE format enabled
P86E 4E
PROGRAM MODE LEVEL
Installer mode or NessComms.
FACTORY DEFAULT
OFF.
NOTES
Audible Voice Format is not available
in the D16x C-Bus model. This model
sends Audible format as a series of
beeps.
See page 70 for more detail.
44
Ness D8x / D16x Control Panel – Installation Manual
PROGRAMMING