NORDAC ON / ON+ (SK 3xxP)Manual with installation instructions
118 BU 0800 en-4521
6.2 Messages
In the following tables you will find a list of possible errors, a description of the cause and instructions
for troubleshooting. Under “Further notes” you will find solution approaches related to
parameterisation.
Error messages
Coding
ERROR TEXT
Cause
Remedy
Group Number
E001
1.0
Inverter overtemp.
Temperature monitoring of the inverter
Temperature range has been exceeded or undershot.
Reduce or increase ambient temperature
Check fan or cabinet ventilation
Check the device for dirt
Further notes:
see (P739) for temperature display
E001
1.1
Intern. inverter temp
Temperature monitoring of the inverter
Temperature range has been exceeded or undershot.
Reduce or increase ambient temperature
Check fan or cabinet ventilation
Check the device for dirt
Further notes:
see (P739) for temperature display
E002
2.0
Motor overtemp. - PTC
The motor temperature sensor (PTC) or the separate PTC
input has triggered.
Reduce motor load
Increase motor speed
Install external motor fan or check the function
Further notes:
Check parameter setting (P425)
E002
2.1
Motor overtemp.I²t
The inverter has detected an impermissible motor
temperature (motor I
2
t).
Reduce motor load
Increase motor speed
Repeat stator resistance measurement 5.1.3 "Motor
data"
E002
2.2
Dig In overtemp.
Thermostat (e.g. from braking resistor) has been triggered.
The digital input is “low”.
Check connection and thermostat