NORDAC ON / ON+ (SK 3xxP) – Manual with installation instructions
108 BU 0800 en-4521
5.1.7 Information
P700 Actual operating status
Indicates the presently active (unacknowledged)
fault.
Indicates a present warning message.
inhibit
Indicates the reason for active switch-on inhibit.
(DS402)
Displays the present active error according to
DS402 terminology.
Messages (coded) for the actual operating status of the frequency inverter such as
faults, warnings or the cause of a switch-on inhibit .
Display of bus-level error messages is in decimal integer format. The displayed value
must be divided by 10 in order to correspond with the correct format.
Example: Display: 20 Error number: 2.0
The error number range from 50.0 to 99.9 displays messages from any extension
modules. The meaning of these numbers is explained in the relevant documentation
for the extension module.
P701 Last fault
“Last fault 1 … 10”. This parameter stores the last 10 faults .
P702 Freq. last error S
[-01] … [-10]
"Frequency last error 1 … 10“. This parameter stores the output frequency that was
being delivered at the time the fault occurred. The values of the last 10 errors are
stored.
P703 Current last error S
[-01] … [-10]
"Current last error 1 … 10“. This parameter stores the output current that was being
delivered at the time the fault occurred. The values of the last 10 errors are stored.
P704 Volt. last error S
“Last voltage error 1 … 10”. This parameter stores the output voltage that was being
delivered at the time the fault occurred. The values of the last 10 errors are stored.
P705 Dc.lnk volt. last er. S
[-01] … [-10]
"Link circuit voltage last error 1 … 10“. This parameter stores the link circuit voltage
that was being delivered at the time the error occurred. The values of the last 10
errors are stored.