5 Parameter
BU 0800 en-4521 97
P516 Skip frequency 1 S P
{ 0.0 }
The output frequency around the frequency in the range between +P517 and -P517
set here is not displayed.
This range is transmitted with the set deceleration and acceleration ramp; it cannot be
continuously supplied to the output.
Frequencies below the absolute minimum frequency should not be set.
P517 Skip freq. area 1 S P
Skip range for "Skip freq. area 1" P516. This frequency value is added and subtracted
from the skip frequency.
Skip range 1: (P516 - P517) ... (P516) … (P516 + P517)
P518 Skip frequency 2 S P
The output frequency around the set frequency in the range between
and -P519 set here is not displayed.
This range is transmitted with the set deceleration and acceleration ramp; it cannot be
continuously supplied to the output.
Frequencies below the absolute minimum frequency should not be set.
P519 Skip range 2 S P
Skip range for "Skip frequency 2" P518. This frequency value is added to and
subtracted from the skip frequency.
Skip range 2: (P518 - P519) … (P518) ... (P518 + P519)