Operating Parameters
B-6
Part 1107600_03
2014 Nordson Corporation
Standard (contd)
13
Change Hose 2 Output to Electric Gun Activation
Description:
Changes the proportioned 240 VAC current that is provided to the hose 1
heater to a switched 240 VAC current that is used to activate a
manifold-mounted electric gun.
Value:
0 (disabled)
1 (enabled)
Resolution:
—
Default Value:
0 (disabled)
Format:
—
Use:
Use only when a Nordson manifold-mounted electric gun is installed and
a switching device is connected to the melter’s switch receptacle. Refer
to the electric gun manual for information on mounting and using the gun.
14
External Communications Lock-out
Description:
Used as a safety feature when performing maintenance on the melter.
Prevents external control of the melter through standard or optional
inputs/outputs or network communications (optional)
Value:
0 (disabled)
or
1 (enabled)
Resolution:
—
Default Value:
0 (disabled
Format:
—
Use:
Set parameter to 1 (enabled) before performing any maintenance on the
melter. When enabled, all external control of the melter stops until the
parameter is once again set to 0 (disabled).