Table 3-6 Power Supply Configuration Settings
Display Function Configuration 1 Configuration 2
ID 00..15
(Unit ID)
Unit ID: Sets unit ID for
network, identifies master
or slave
Master = ID 00 Slaves = ID 01..15
For a standalone power supply, set the unit ID to 00. For networked power supplies,
set the master to 00 and set the slaves to 01, 02.....15.
S Each power supply on a network must have a unique ID number.
FLT
(Fault)
Fault State: Sets Unit Fault
to fault units separately or
all together
FLT U = FAULT UNIT
(Fault this unit only)
FLT A = FAULT ALL
(Shuts down all units on
the network)
This setting is for multiple system master/slave networks. A networked power supply
in a fault condition can fault only itself or the entire network.
S All networked power supplies must have the same fault setting.
RFD
(RF Detector)
Sets RF detector status for
each power supply
RFD Y = RF Detector
connected
RFD N = No RF detector
connected
A Master power supply is automatically set to RFD Yes. Slave power supplies can be
set to Yes or No. Only one RF detector is required for a network.
NT
(Network)
Specifies network
communication protocol
NT CAN = CAN BUS
protocol
NT 485 = 485 protocol
The CAN BUS protocol is the preferred protocol for power supply networks.
It must be selected for any network using DeviceNet.
S All power supplies on the network must be set to the same protocol.
CTRM Can termination CTRM Y = CAN
termination Yes.
CTRM N = CAN
termination No.
Internal network termination setting.
S Set to Yes for networked units that have only one network port connected (and so
are on one end of the network).
S Set to No for all networked units that have both network ports connected.
S The Master power supply is typically on one end of the network.
ANA Remote Power Level
Control enable/setting
ANA Y = Y (yes) ANA N = N (no)
Refer to Table 3-3 on page 3-7 for connections.
S If set to ANA Y, then the next setting allows you to choose the input. When in
Remote mode, light output is controlled by the input to the AIN and ACOM
terminals (5 and 4).
S If set to ANA N, then the light output is controlled from the power supply front panel
in both Remote and Local modes.
IN Analog input selector mA = 4−20 mA control V = 0−10 Vdc control
Specifies the input type for Remote Power Level Control. This selection appears if
ANA Y is selected. Refer to Table 3-3 on page 3-7 for connections.
CTL Remote control source IO = Use discrete remote
I/O terminal
DN = Use DeviceNet for
remote control
Refer to Table 3-3 on page 3-7 for discrete remote I/O connections. IO is the default
setting.