Operating Parameters
B-9
Part 1126931_01
2018 Nordson Corporation
Input Setup
30
Input 1
Description:
Control options that determine the function of input 1.
Value:
0 - Input Disabled
1 – Standby On/Off
2 – Heaters On/Off
3 – Motor 1 Enable/Disable
4 – Hose/Applicator 1 Enable/Disable
5 – Hose/Applicator 2 Enable/Disable
6 – Hose/Applicator 3 Enable/Disable
7 – Hose/Applicator 4 Enable/Disable
8 – Hose/Applicator 5 Enable/Disable
9 – Hose/Applicator 6 Enable/Disable
10 – Automatic standby
11 - Motor 2 Enable/Disable
Resolution:
1
Default Value:
10
Format:
Use:
If Motor Enable/Disable (3) is selected, the motor will turn on whenever voltage
is present on the input contacts. To require that the pump key be pressed (pump
enabled) and that there be voltage on the input contacts before the motor can
turn on, set the value of parameter 8, Automatic Pump On to 0 (disabled).
Refer to Installing Melter Inputs in Section 3, Installation, for information about
setting up inputs.
NOTE: Only Input 1 offers control option 10.
Multiple inputs can be set to the same input value. After one or more inputs that
have the same input value are energized, the input functionality will not be
considered inactive (off) until all of the inputs with the same input value are
de‐energized (Multiple inputs set to the same input value are logical ORed.).