DuraBlue‐II service kit motor drive
keypad
PAR 430
Analog Input 1
REM AUTO SET
8
Installation
3-33
Part 1126931_01
2018 Nordson Corporation
Programming
This parameter comes pre‐set at the factory.
Use the service kit motor drive keypad, PN 7411739 to set up the motor run
status monitoring for each motor. Refer to Changing a Motor Drive Parameter
in Section 6, Troubleshooting, for a detailed procedure for changing a motor
drive parameter.
1. Press
(ENT) until the Group Screen is displayed.
2. Press
(UP) until Group 4 is displayed.
3. Press
(ENT) to access I/O parameters.
4. Press
(UP) to select the parameter until “P420.00” is displayed.
5. Press
(ENT) to select the sub parameter.
6. Press
(UP) to select P420.01.
7. Press
(ENT) to set parameter.
8. Press
(UP) to change parameter until 51 is displayed.
9. Press
(ENT) >3S to save parameters to memory.