Operating Parameters
B-14
Part 1126931_01
2018 Nordson Corporation
50 Current Day
Description:
Used to set the current day of the week.
Value:
1 to 7 (1 = Monday, 2 = Tuesday, etc.)
Resolution:
1
Default Value:
—
Format:
—
Use:
Refer to Section 4, Operation, Function Keys, for information about the use and
affects of the seven‐day clock feature.
51 Current Time
Description:
Used to set the local time of the day.
Value:
0000 to 2359 (European time format)
Resolution:
1 minute
Default Value:
(Time set at factory)
Format:
Hours, Hour: Minute, Minute
Use:
This setting only needs to be made once for all daily schedules
55 Schedule 1 Heaters On
Description:
Used to set the time that the clock will turn on the heaters during schedule 1.
Value:
0000 to 2359, ‐ ‐ ‐ ‐
Resolution:
1 minute
Default Value:
0600
Format:
Hours, Hour: Minute, Minute
Use:
Set the desired time for the heaters to turn on.
To disable this parameter, set the parameter's value to “‐ ‐ ‐ ‐” by simultaneously
pressing both of the right‐display scroll keys.
56 Schedule 1 Heaters Off
Description:
Used to set the time that the clock will turn off the heaters during schedule 1.
Value:
0000 to 2359, ‐ ‐ ‐ ‐
Resolution:
1 minute
Default Value:
1700
Format:
Hours, Hour: Minute, Minute
Use:
To disable this parameter, set the parameter's value to “‐ ‐ ‐ ‐” by simultaneously
pressing both of the right‐display scroll keys.