Installation
3-14
Part 1126931_01
2018 Nordson Corporation
Quick Setup (contd)
Table 3‐2 Common Operating Parameters
Parameter Parameter Name Purpose Default Value
4 Ready Delay Time
A timer that delays the activation of the ready LED for
a pre‐defined time period after the tank, hoses, and
applicators are at the desired set‐point temperature.
The ready delay timer will only activate if the
temperature of the tank, at the time the melter is turned
on, is below its assigned set‐point temperature by
27 C (50 F) or more.
0 minutes
5
Service Interval
Time
A timer that turns on a service LED when the value set
for the timer equals the number of hours that the
heaters have been on. The service LED is used to
signal the need for maintenance.
500 hours
7 Motor Off Delay
If the switch receptacle is used, this parameter
determines the amount of time the motor will remain
on after the switched device is turned off.
0 seconds
8 Automatic Pump On
Allows the pump to start automatically when system
ready is reached, provided that the pump has been
enabled by pressing the pump key.
Enabled
11 Create Password
Sets a password that must be entered before any
melter operating parameter or set‐point temperature
can be changed.
5000
20 Temperature Units
Sets the units of the temperature display to degrees
Celsius(C) or to degrees Fahrenheit (F).
C
21
Over Temperature
Delta
Sets the number of degrees that any heated
component can exceed its assigned set‐point
temperature before an over temperature fault occurs.
15 C (25 F)
22
Under Temperature
Delta
Sets the number of degrees that any heated
component can drop below its assigned set‐point
temperature before an under temperature fault occurs.
25 C (50 F)
23 Standby Delta
Sets the number of degrees that the temperature of all
heated components will be decreased when the melter
is placed into the standby mode.
50 C (100F)
26
Manual Standby
Time
Sets the amount of time the melter will remain in the
standby mode after the standby key is pressed.
Disabled
50 to 77 Seven‐day Clock
A group of parameters that control the melter's clock.
The clock is used to automatically turn the heaters on
and off and to place the melter into the standby mode.
Disabled