Tank, hose, and applicator keys
Operation
4-19
Part 1126931_01
2018 Nordson Corporation
To adjust the setpoint temperature using the global‐by‐component
method
1. Press and hold the Hose or Applicator key for three seconds.
The left display indicates the number of the first sequential hose or
applicator. The right display indicates the current set‐point temperature of
the hose or the applicator.
2. Scroll the left display to 0.
The right display indicates all dashes (‐ ‐ ‐ ‐).
3. Press the Enter key.
The right display flashes.
4. Use the keypad to enter the set‐point temperature recommended by
the manufacturer of the hot melt.
NOTE: If the keypad or the right‐display scroll keys have no affect on the
right display, the melter is password protected. You must enter a valid
password before you can change set‐point temperatures. Refer to
Entering a Password in this section.
5. Press the Enter key.
The hoses or the applicators begin to heat or cool to their new
set‐point temperature.