HQGL[*7
H &RGHV
Type Codes for Output Devices
100 AFC-600 Programming PN 51032:A 3/8/99
1$&DQG3DQHO&LUFXLW7
H&RGHV
1RWH
)RU LQVWUXFWLRQV RQ
UR
UDPPLQ
7
H &RGHV UHIHU
WR +RZ WR 0RGLI
RU 'HOHWH D
3RLQW
32,17
RQ
D
H
Table 48 contains a comprehensive list of Type Codes for NACs and Panel Circuits. The
Type Codes that display, however, depend on the type of circuit: NAC or Panel Circuit
relay.
7DEOH 1$& DQG 3DQHO &LUFXLW 7
H &RGHV
Type Code Configuration Function
CONTROL
Panel Circuit relay or NAC Supervised NAC
RELAY
Panel Circuit relay only Relay output
BELL
CIRCUIT
Panel Circuit relay or NAC Supervised NAC for
notification appliance
STROBE
CKT
Panel Circuit relay or NAC Supervised NAC for
notification appliance
HORN
CIRCUIT
Panel Circuit relay or NAC Supervised NAC for
notification appliance
AUDIBLE
CKT
Panel Circuit relay or NAC Supervised NAC for
notification appliance
SPEAKER
Panel Circuit relay only Supervised NAC for speaker
circuits
REL
END
BELL
Panel Circuit relay or NAC Supervised NAC
blank label Panel Circuit relay or NAC Supervised NAC for undefined
device
RELEASE
CKT
Panel Circuit relay or NAC Releasing circuit, nonpower-
limited, supervised for opens,
shorts, and ground faults
REL
CKT
ULC
Panel Circuit relay or NAC Releasing circuit, power-
limited, supervised for opens,
shorts, and ground faults
RELEA
.
FORM
C
Panel Circuit relay only Relay output, contacts operate
upon release
REL
AUDIBLE
Panel Circuit relay or NAC NAC, activated upon release
TELEPHONE
Panel Circuit relay only Standard telephone circuit
REL
CODE
BELL
NAC only Supervised NAC (MPS-6 NAC
only)
INSTANT
RELE
Panel Circuit relay or NAC NAC, short=normal;
supervised for open circuits
and ground faults. Always
non-silenceable and switch-
inhibited.
Technical Manuals Online! - http://www.tech-man.com