How to Program a Releasing Zone
$
HQGL[ $ 5HOHDVLQ
$
OLFDWLRQV
AFC-600 Programming PN 51032:A 3/8/99 55
+RZ WR 3UR
UDP DQ
$ERUW 6ZLWFK
The following contains information needed to program an Abort Switch for a monitor
module.
Description
A monitor module, connected to a UL-listed abort station (such
as the Notifier ARA-10), that you use as an abort switch for a
Releasing Zone. You can program multiple monitor modules with
the
ABORT
SWITCH
Type Code that work like multiple
conventional abort switches on a conventional zone.
How to program
1. Select a monitor module that you want to use as an Abort
Switch (refer to "How to Modify or Delete a Point
(2=
POINT
)" on page 21).
2. Select the
ABORT
SWITCH
Type Code.
3. Select the Releasing Zone (R0-R9) for your releasing
application.
4. Press the
ENTER
key to save, then press the
ESC
key until you
return to the Program Change screen.
5. Select the type of Abort Switch for your releasing
application (refer to "How to Program an Abort Switch" on
page 46).
Example
Figure 67
illustrates a programming example of a monitor module
programmed as an Abort Switch for Releasing Zone R5.
)LJXUH 0RQLWRU 0RGXOH &RQILJXUHG DV DQ $ERUW 6ZLWFK
352*50 $%257 6:,7&+ 02'8/( $''5 0
= =5 = = = 0
7
H &RGH VHOHFWLRQ
$%257 6:,7&+
5HOHDVLQ
=RQH VHOHFWLRQ 5 VKRZQ
7
H &RGH
$%257 6:,7&+
'HWHFWRU
5
FRQWURO
$5$ VWDWLRQ ZLWK $ERUW 6ZLWFK
PRQLWRU
%
PRGXOH
PRGXOH
Technical Manuals Online! - http://www.tech-man.com