Field-Wiring the Modules
,QVWDOODWLRQ
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 2-29
)LHOG:LULQJDQ2SWLRQDO$9363RZHU6XSSO\
$936 :LULQJ
2YHUYLHZ
This section covers wiring an AVPS-24. Use TB2 terminals for a power circuit run to
CMX control modules. Table 2-10 lists connections between the AVPS-24 and the
MPS-400. For wiring, see Figure 2-38, Figure 2-39, or both.
Table 2-10 AVPS-24 to MPS-400 Connections
$936 :LULQJ
'LDJUDPV
Plug the Auxiliary Bell Power Harness to the connector J5 on the ICM-4 or the ICE-4
NAC modules as shown in Figure 2-38:
)LJXUH  :LULQJ DQ $936 WR DQ ,&( RU DQ ,&0
Figure 2-39 shows a block diagram for connecting or changing multiple AVPS-24
power supplies:
)LJXUH  :LULQJ 0XOWLSOH $936V
AVP S-2 4
Pin
Function Connect to MPS-400...
TB1-1 Earth ground in Chassis or earth ground
terminal
TB1-2 Secondary power (24 VDC) positive (+) connection TB1-6 (+)
TB1-3 Secondary power (24 VDC) negative (–) connection TB1-7 (–)
TB1-4 Primary power (120 VAC) neutral connection TB-2 (neutral)
TB1-5 Primary power (120 VAC) hot connection TB1-4 (hot)
TB1-6 Earth ground out TB1-3 (earth ground)
7URXEOH /('
1RWH 7KH $X[LOLDU\ %HOO
3RZHU +DUQHVV SURYLGHV
9'& VSHFLDO SXUSRVH
SRZHUXQILOWHUHGXQUHJXODWHG
SRZHUOLPLWHG  $
PD[LPXP WR 1$& PRGXOHV
$X[LOLDU\ %HOO 3RZHU +DUQHVV
31 
,&( PRGXOH
%ODFN ZLUH%OXH ZLUH
7HUPLQDO 7%
7HUPLQDO 7%
,&0 PRGXOH
7R - $X[ 7URXEOH
RQ WKH 036
$936  PRGXOH
7R - $X[ 7URXEOH
RQ WKH 036
/DVW $936
)LUVW $936
www.PDF-Zoo.com