Wiring a Signaling Line Circuit (SLC)
,QVWDOODWLRQ
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 2-45
:LUH5HTXLUHPHQW VIRUD)RXU:LUH6/&
0HDVXULQJ /RRS
5HVLVWDQFH IRU D )RXU
:LUH 6/&
The total DC resistance of the SLC pair cannot exceed 40 ohms. Measure DC
resistance as shown in Figure 2-62.
1RWH )RU GHWDLOHG ZLULQJ
UHTXLUHPHQWV UHIHU WR
$SSHQGL[ %
1. Disconnect the SLC Out and SLC Return at the control panel.
2. Short the two leads of SLC Return.
3. Measure the resistance across the SLC Out leads (Figure 2-62).
)LJXUH  0HWHU /HDGV IRU 0HDVXULQJ D )RXUZLUH 6/&
0HDVXULQJ 7RWDO :LUH
/HQJWK IRU D )RXUZLUH
6/&
The total length of wire (12 AWG) in a four-wire SLC cannot exceed 10,000 feet.
Figure 2-63 identifies the output and return loops from SLC terminal TB5 on the CPU:
)LJXUH  0HDVXULQJ WKH :LUH /HQJWK ² )RXU:LUH 6/&
6/& 2XW
6/& 5HWXUQ
1RWH 77DSSLQJ LV QRW DOORZHG RQ D
IRXUZLUH 6/&
&38
&38 RQO\
6/& $ ORRS UHWXUQ
6/& % RXWSXW ORRS
QR FRQQHFWLRQ
www.PDF-Zoo.com

Table of Contents

Other manuals for Notifier AFP-400

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFP-400 and is the answer not in the manual?

Notifier AFP-400 Specifications

General IconGeneral
BrandNotifier
ModelAFP-400
CategoryControl Panel
LanguageEnglish

Related product manuals