Wiring a Signaling Line Circuit (SLC)
,QVWDOODWLRQ
AFP-300/AFP-400 Installation PN 50253:C1 05/22/97 2-47
6W\OH :LULQJ 2YHUYLHZ
Obtain Style 7 operation by using Isolator Bases (B524BI or B224BI) with each
detector flanking MMX modules with ISO-X modules (Figure 2-65). Wire-to-wire
shorts on the SLC do not prevent the control panel from receiving alarm signals.
Do not T-Tap or branch a Style 7 four-wire SLC. Ratings and characteristics are
identical to a NFPA Style 6 four-wire SLC. Table 2-20 shows connections between the
SLC and CPU terminal TB-5:
Table 2-20 SLC to CPU Connections
6W\OH :LULQJ 'LDJUDP
Figure 2-65 shows typical wiring for a Style 7 SLC with ISO-X modules flanking
MMX modules:
)LJXUH  6W\OH )RXU:LUH 6/& XVLQJ ,62; 0RGXOHV
Connect... To CPU...
SLC Out TB5-1 (+)
TB5-3 (–)
SLC Return TB5-2 (+)
TB5-4 (–)
'HWHFWRU LQ ,VRODWRU
%DVH
'HWHFWRU LQ ,VRODWRU
%DVH
'HWHFWRU LQ ,VRODWRU
%DVH
&38
0DQXDO 3XOO 6WDWLRQ ZLWK
00; IODQNHG E\ ,62;
PRGXOHV
,62; ,VRODWRU 0RGXOH
,62; ,VRODWRU 0RGXOH
'HWHFWRU LQ ,VRODWRU
%DVH
1RWH (QFORVH DOO ZLULQJ EHWZHHQ
D PDQXDO SXOO VWDWLRQ DQG ,62;
PRGXOHV LQ FRQGXLW