5-181
5-14 Other Functions
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
5
Functions
A093 1st Deceleration
Time 2
0.01 to 3,600.00 [s] 10.00 0.01 to 3,600.00 [s] 15.00
A293 2nd Deceleration
Time 2
0.01 to 3,600.00 [s] 10.00
0.01 to 3,600.00 [s] 15.00
A095 2-step Acceleration
Frequency 1
0.00 to 400.00 [Hz] 0.00 0.00 to 1,000.00 [Hz]
0.00
A295 2-step Acceleration
Frequency 2
0.00 to 400.00 [Hz] 0.00 0.00 to 1,000.00 [Hz]
0.00
A096 2-step
Deceleration
Frequency 1
0.00 to 400.00 [Hz] 0.00 0.00 to 1,000.00 [Hz]
0.00
A296 2-step
Deceleration
Frequency 2
0.00 to 400.00 [Hz] 0.00 0.00 to 1,000.00 [Hz]
0.00
A101 FI Start Frequency 0.00 to 400.00 [Hz] 0.00 0.00 to 1,000.00 [Hz]
0.00
A102 FI End Frequency 0.00 to 400.00 [Hz] 0.00 0.00 to 1,000.00 [Hz]
0.00
A145 Frequency Addition
Amount Setting
0.00 to 400.00 [Hz] 0.00 0.00 to 1,000.00 [Hz]
0.00
A154 Deceleration Stop
Frequency
0.00 to 400.00 [Hz] 0.00 0.00 to 1,000.00 [Hz]
0.00
A156 PID Sleep Function
Operation Level
0.00 to 400.00 [Hz] 0.00 0.00 to 1,000.00 [Hz]
0.00
A161 VR Start
Frequency
0.00 to 400.00 [Hz] 0.00 0.00 to 1,000.00 [Hz]
0.00
A162 VR End Frequency 0.00 to 400.00 [Hz] 0.00 0.00 to 1,000.00 [Hz]
0.00
b007 Frequency
Matching Lower
Limit Frequency
Setting
0.00 to 400.00 [Hz] 0.00 0.00 to 1,000.00 [Hz]
0.00
b019 Free-electronic
Thermal
Frequency 3
Free-electronic Thermal
Frequency 2 to 400 [Hz]
0.0 Free-electronic Thermal
Frequency 2 to 1,000 [Hz]
0.0
b054 Freq. Drop to Start
Ctrl. Decel
0.00 to 10.00 [Hz] 0.00 0.00 to 100.00 [Hz]
0.00
b082 Starting Frequency 0.10 to 9.99 [Hz] 0.50 0.10 to 100.00 [Hz]
0.50
b083 Carrier Frequency 2.0 to 15.0 [kHz] 10.0 2.0 to 10.0 [kHz] 5.0
b112 Free V/f Frequency
7
Free V/f Frequency 6 to 400
[Hz]
0. Free V/f Frequency 6 to
1,000 [Hz]
0.
C027 MP Selection 00: Output frequency
01: Output current
02: Output torque
03: Digital output frequency
04: Output voltage
05: Input power
06: Electronic thermal load
rate
07: LAD frequency
08: Digital current monitor
10: Cooling fin temperature
12: Do not use this setting.
15: Pulse train input monitor
16: Optional board
07 00: Output frequency
01: Output current
03: Digital output frequency
04: Output voltage
05: Input power
06: Electronic thermal load
rate
07: LAD frequency
08: Digital current monitor
10: Cooling fin temperature
12: Do not use this setting.
15: Pulse train input monitor
16: Optional board
07
Parameter
No.
Function name
Normal Mode with a Heavy Load
Rating (CT)
High-frequency Mode
Setting range
Default
Setting range
Default