6 Drive Programming Commands
6 - 38
Drive Programming User’s Manual (I580-E2)
Example
In the above example, the status of X(00) to X(02) is monitored with the parameter UMon(0) (d025), and X(02) is output to Y(00).
Y(i) value
Command Description Argument
Outputs data to the output terminal variable in
units of bits.
i: output terminal variable
(range 0 to 6)
Value: any variable or constant
Format
Flowchart method Text language method
Y(i) : <value>
Note The output terminal variable is a variable that controls the status of the inverter's output termi-
nal. The following settings are required. The numerical order of the output terminal variables
follows the numerical order of the set general-output numbers.
MX2:
Set the Multi-function Output P1 and P2 Selection (C021 and C022) and the Multi-function Relay Out-
put (MA, MB) Function Selection (C026) to 44 to 46 (MO1 to MO3: General-purpose output).
RX: Set the Multi-function Output P1 to P5 Selection (C021 to C025) and the Multi-function Relay Out-
put (MA, MB) Function Selection (C026) to 44 to 49 (MO1 to MO6: General-purpose output).
<Assignment example>
Y(00) MO1 (multi-function No. 44)
Y(01) MO2 (multi-function No. 45)
Y(02) MO3 (multi-function No. 46)
Y(03) MO4 (RX only: multi-function No. 47)
Y(04) MO5 (RX only: multi-function No. 48)
Y(05) MO6 (RX only: multi-function No. 49)
For details, refer to 5-2 Input/Output Terminal Variables on page 5-5.
Flowchart Text
Block number
Operation
1 Assigns 0 to UBw.
2 to 4 Assigns the variables X(00) to X(02) to the variables UB(0) to UB(2).
5 Assigns UBw to UMon(0).
6 Assigns UB(2) to Y(00).
7 Jumps to the block 1: loop_ unconditionally.
Y(i) : <value>