8 Overview of Built-in Functions and Allocations
CP1E CPU Unit Software User’s Manual(W480)
8-3 Terminal Allocations for Built-in Functions
8
8-3-3 Allocating Built-in Input Terminals
E14 or N14 CPU Units
E10 CPU Units
Note 1 The same pulse inputs must be used for high-speed counter 0 and high-speed counter 1.
2 High-speed counter 2 cannot be used if the input setting of high-speed counter 0 or high-speed counter 1
is set for differential phase inputs (4×), pulse + direction inputs, or up/down pulse inputs.
Termi-
nal
block
label
Terminal
number
PLC Setup
Interrupt input settings on Built-in Input Tab
Page
High-speed counter 0 to 3 settings on Built-
in Input Tab Page
Origin search set-
tings on Pulse
Output 0/1 Tab
Page
Normal Interrupt Quick Use Use
Normal input
Interrupt
inputs
Quick-
response
inputs
Increment
pulse input
Differential
phase ×4 or
up/down
Pulse/direc-
tion
Origin search
CIO 0
00
Normal input 0
−−
Counter 0,
increment input
Counter 0,
phase A or up
input
Counter 0,
pulse input
01
Normal input 1
−−
Counter 1,
increment input
Counter 0,
phase B or
down input
Counter 1,
pulse input
02
Normal input 2 Interrupt
input 2
Quick-
response
input 2
Counter 2,
increment input
Counter 1,
phase A or up
input
Counter 0,
direction
03
Normal input 3 Interrupt
input 3
Quick-
response
input 3
Counter 1,
phase B or
down input
Counter 1,
direction
Pulse 0, Origin
proximity input signal
04
Normal input 4 Interrupt
input 4
Quick-
response
input 4
Counter 3,
increment input
Counter 0,
Phase Z or
reset input
Counter 0,
reset input
05
Normal input 5 Interrupt
input 5
Quick-
response
input 5
Counter 4,
increment input
Counter 1,
Phase Z or
reset input
Counter 1,
reset input
Pulse 1, Origin
proximity input signal
06
Normal input 6 Interrupt
input 6
Quick-
response
input 6
Counter 5,
increment input
−−
Pulse 0: Origin input
signal
07
Normal input 7 Interrupt
input 7
Quick-
response
input 7
−−
Pulse 1: Origin input
signal
Termi-
nal
block
label
Terminal
number
PLC Setup
Interrupt input settings on Built-in Input Tab
Page
High-speed counter 0 to 3 settings on Built-
in Input Tab Page
Normal Interrupt Quick Use
Normal input
Interrupt
inputs
Quick-
response
inputs
Increment
pulse input
Differential
phase ×4 or
up/down
Pulse/direc-
tion
CIO 0 00
Normal input 0
−−
Counter 0,
increment input
Counter 0,
phase A or up
input
Counter 0,
pulse input
01
Normal input 1
−−
Counter 1,
increment input
Counter 0,
phase B or
down input
Counter 1,
pulse input
02
Normal input 2 Interrupt
input 2
Quick-
response
input 2
Counter 2,
increment input
Counter 1,
phase A or up
input
Counter 0,
direction
03
Normal input 3 Interrupt
input 3
Quick-
response
input 3
Counter 1,
phase B or
down input
Counter 1,
direction
04
Normal input 4 Interrupt
input 4
Quick-
response
input 4
Counter 3,
increment input
Counter 0,
Phase Z or
reset input
Counter 0,
reset input
05
Normal input 5 Interrupt
input 5
Quick-
response
input 5
Counter 4,
increment input
Counter 1,
Phase Z or
reset input
Counter 1,
reset input