17 Ethernet Option Board
17-38
CP1E CPU Unit Software User’s Manual(W480)
The default setting for Address Conversion Mode of the Ethernet Option Board is
Auto (Dynamic), so slecet Auto-detect in the field of Workstation Node Number.
Therefore, according to computer's IP address, computer's FINS node address is set
automatically in the CX-Programmer. At that time, IP address post number and FINS
node address are the same.
In this example, 2 is displayed according to the host number of computer's IP
address 192.168.250.2 set by manual, and it is invalid to change the setting.
Set IP address to 192.168.250.1, which is the Ethernet Option Board's IP address.
Set FINS/UDP Port to 9600 (default), which is the UDP port number in the FINS
communications service.
4
Connect the target PLC online
Select Work Online in the PLC menu.