Appendices
A-68
CP1E CPU Unit Software User’s Manual(W480)
A402 10 PLC Setup Error Flag
(non-fatal error)
ON when there is a setting error in the
PLC Setup. The CPU Unit will continue
operating and the ERR/ALM indicator
on the front of the CPU Unit will flash.
Note This flag will be turned OFF when
the error is cleared.
ON: Error
OFF: No error
Cleared Cleared Refreshed
when error
occurs.
15 FAL Error Flag
(non-fatal error)
ON when a non-fatal error is generated
by executing FAL. The CPU Unit will
continue operating and the ERR/ALM
indicator on the front of the CPU Unit
will flash.
The bit in A360 to A391 that corre-
sponds to the FAL number specified in
FALS will be turned ON and the corre-
sponding error code will be written to
A400. Error codes 4101 to 42FF corre-
spond to FAL numbers 001 to 2FF (0 to
511).
Note This flag will be turned OFF when
the error is cleared.
ON: FAL error
occurred
OFF: FAL not exe-
cuted
Cleared Cleared Refreshed
when error
occurs.
A360 to
A391,
A400
A403 00 to
08
Memory Error Location When a memory error occurs, the
Memory Error Flag (A401.15) is turned
ON and one of the following flags is
turned ON to indicate the memory area
where the error occurred
A403.00: Ladder program
A403.04: PLC Setup
When a memory error occurs, the CPU
Unit will continue operating and the
ERR/ALM indicator on the front of the
CPU Unit will flash.
Note The corresponding flag will be
turned OFF when the error is
cleared.
ON: Error
OFF: No error
Cleared Cleared Refreshed
when error
occurs.
A401.15
10 Backup Memory Error
Flag
ON when the built-in EEPROM backup
memory is physically destroyed.
ON: Error
OFF: No error
Cleared Cleared Refreshed
when error is
detected.
A404 I/O Bus Error Details Contains information on I/O bus errors.
The CPU Unit will stop operating and
the ERR/ALM indicator on the front of
the CPU Unit will light.
Note A401.14 (I/O Bus Error Flag) will
turn ON.
0A0A hex: Expan-
sion Unit error
Cleared Cleared Refreshed
when error is
detected.
A401.14
A407 13 to
15
Too Many I/O Points,
Cause
The 3-digit binary value of these bits
indicates the cause of the Too Many
I/O Points Error.
010: Too many
Expansion Unit and
Expansion I/O Unit
words
Cleared Cleared Refreshed
when error
occurs.
A401.11
A424 00 to
15
Error Option Board
Flags
The bit corresponding to the option slot
turns ON when an error occurs in an
Option Board (A315.13 will be ON).
Bit 01: Option slot 2
ON: Error
OFF: No error
Cleared Cleared A353.13
A434 0 Open-circuit Detection
for Built-in Analog
Input 0
On when AD0 open-circuit is detected Retained Cleared Refreshed
when AD0
open-circuit is
detected.
1 Open-circuit Detection
for Built-in Analog
Input 1
On when AD1 open-circuit is detected Retained Cleared Refreshed
when AD1
open-circuit is
detected.
4 Built-in Analog Initial
Flag
ON when the built-in analog initializa-
tion is normally finished.
Retained Cleared Refreshed
when built-in
analog initial-
ization is nor-
mally finished.
Address
Name Function Settings
Status
after
mode
change
Status at
startup
Write
timing
Related
flags,
settings
Words Bits