84
Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks Section 4-4
The following diagram shows the wiring of the DRT1-MD16TA-1 Remote I/O
Terminal.
Note 1. V1 is not connected internally to V2, and G1 is not connected internally to
G2. Connect them carefully
2. When using inductive loads (such as solenoids or valves), use a load with
a built-in diode to absorb reverse power or attach a diode externally.
3. Line colors have been changed accompanying changes in JIS standards
for photoelectric and proximity sensors. Previous colors are given in paren-
theses.
Dimensions The following diagram shows the dimensions for the DRT1-MD16TA and
DRT1-MD16TA-1 Remote I/O Terminals. All dimensions are in mm.
Note The circuit section can be removed by loosening the circuit removal screws.
(Refer to Components of the DRT1-MD16TA and DRT1-MD16TA-1.)
7
V2
G2
1
V2
G2
0
V2
G2
V2
G2
−+
7
V1
G1
1
V1
G1
0
V1
G1
V1
G1
−+
Black (white)
Brown (red)
Blue (black)
Blue (black)
Brown (white)
Solenoid,
valve, etc.
Solenoid,
valve, etc.
3-wire sensor with
PNP output
(photoelectric or
proximity sensor)
2-wire sensor
(e.g., limit switch)
Two, 4.2 dia. or M4
Mounting holes
170±0.2
40±0.2
58
(83)
180
50
(54)
0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7
OUTIN
DRT1-MD16TA
REMOTE TERMINAL DC24V
NS
MS
DR0
ON
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
DR1 HOLDNC
Values in parentheses
are reference values.