70
Transistor Remote I/O Terminals with 3-tier I/O Terminal Blocks Section 4-4
Always turn OFF the communications, internal, and I/O power supplies before
removing or attaching the circuit section.
4-4-4 Transistor Remote Output Terminals with 16 Points and 3-tier I/O
Terminal Blocks: DRT1-OD16T (NPN) and DRT1-OD16T-1 (PNP)
Output Specifications
Components of the DRT1-OD16T and DRT1-OD16T-1
Item Specification
Model DRT1-OD16T DRT1-OD16T-1
Internal I/O common NPN PNP
Output points 16 points
Rated output current 0.5 A/point
Residual voltage 1.2 V max. (at 0.5 A,
between each output termi-
nal and G)
1.2 V max. (at 0.5 A,
between each output termi-
nal and V)
Leakage current 0.1 mA max.
ON delay time 0.5 ms max.
OFF delay time 1.5 ms max.
Number of circuits 8 points with two commons
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
OUT
DeviceNet Indicators
DIP switch
DIN track mounting hooks
Communications
connector
Output indicators
Indicate the output status of each contact.
(Lit when the output is ON.)
Terminal block
Pins 1 and 2: Baud rate setting
Pin 3: Reserved (Always OFF.)
Pin 4: Hold/Clear outputs for communications error
DRT1-OD16T
REMOTE TERMINAL DC24V
NS
MS
DR0
ON
DR1 HOLDNC
(Refer to page 312.)
(Refer to page 62.)
Rotary switches (Refer to page 62.)
Set the node address.
Internal power supply terminals
Circuit removal screws.