Setting and Wiring Hardware Section 2-3
Mounting The Master Unit is mounted to the Backplane of the PLC in the same way as
other Units are normally mounted. For details on mounting Master Units to
PLCs, and mounting control panels to PLCs, refer to the applicable CPU Unit
Operation Manual.
2-3-2 Mounting and Setting Slaves
Settings The following example shows Slave settings. For details on how to set
Slaves, refer to SECTION 4 General-purpose Slaves to SECTION 6 Special I/
O Slave Units Specifications.
• DRT-ID16 Remote I/O Terminals (Transistor Inputs)
Node Address: 01
Baud Rate: 125 kbps
• DRT-OD16 Remote I/O Terminals (Transistor Outputs)
Node Address: 02
Baud Rate: 125 kbps
Hold/Clear Outputs for Communications Error:
Clear
• DRT1-TS04T Temperature Input Terminals
Node Address: 03
Baud Rate: 125 kbps
Temperature Scale:
°C
Display Mode for 2 Digits Below Decimal Point:
Normal mode
• C200HW-DRT21 I/O Link Units
Node Address: 07
Unit Number: 0
Baud Rate: 125 kbps
Write Area Handling for Communications Error:
Clear
• DRT1-232C2 RS-232C Units
Node Address: 08
Baud Rate: 125 kbps
C200HW-DRM21-V1
Master Unit (Node 00)
C200HW-DRT21 I/O
Link Unit (Node 07)
DRT1-232C2 RS-232C Unit
(allocated 1 input word)
(Node 08)
DRT1-TS04T Temperature
Input Terminal with 4 inputs
(allocated 4 words)
(Node 03)
DRT1-ID16 Remote I/O Terminal
16 transistor inputs
(Node 01)
DRT1-OD16 Remote I/O Terminal
16 transistor outputs
(Node 01)