Waterproof Terminals (IP67) Section 5-4
Dimensions The following diagram shows the dimensions for the DRT1-OD08CL and
DRT1-OD08CL-1 Waterproof Terminals. All dimensions are in mm.
5-4-6 Mounting in Control Panels
Use screws to mount a Waterproof Terminal in a control panel. These Termi-
nals cannot be mounted on a DIN Track.
Drill the mounting holes in the control panel according to the dimensions
shown in the dimensions diagrams and secure the Terminal with M5 screws.
The appropriate tightening torque is 1.47 to 1.96 N
m.
Installation Direction The Terminal can be mounted in any direction. Any one of the following 6
directions is acceptable.
5-4-7 Wiring Internal Power Supplies, I/O Power Supplies, and I/O Lines
Wiring the Internal Power
Supply and I/O Power
Supply
The internal power supply shares the communications power supply, so it isn’t
necessary to connect a separate internal power supply.
To provide the I/O power supply, connect the external power supply to the Ter-
minal with an XS2-series Round Waterproof Connector listed in the following
table.
160
45
30
54
10
150±0.2
NS
I/O PWR
OUT
MS
Bus
DRT1
10.5±0.1 10.5±0.1
Mounting holes
Three, 4.0 dia. or M5
NS
I/O PWR
IN
MS
Bus
DRT1
NS
I/O PWR
IN
MS
Bus
DRT1
NS
I/O PWR
IN
MS
Bus
DRT1
NS
I/O PWR
IN
MS
Bus
DRT1
Vertical