329
Using Another Company’s Master Unit Appendix B
Connection Object (0x05)
Item DeviceNet service Parameter option
Object instance 1
(Instance type
Static I/O)
Service 0EGet_Attribute_Single No
Object class Attribute Not supported
Service Not supported
Max. number of active connections 1
Item Section Information Max. number of instances
Object instance 1 Instance type Explicit Message 1
Production trigger Cyclic ---
Transport type Server ---
Transport class 3 ---
Item ID content Get
(read)
Set
(write)
Value
Object instance 1 Attribute 1 State Yes No ---
2 Instance type Yes No 00 (hexadecimal)
3 Transport class trigger Yes No 83 (hexadecimal)
4 Produced connection ID Yes No ---
5 Consumed connection ID Yes No ---
6 Initial comm. characteristics Yes No 21 (hexadecimal)
7 Produced connection size Yes No 0D00 (hexadecimal)
8 Consumed connection size Yes No 0D00 (hexadecimal)
9 Expected packet rate Yes Yes ---
12 Watchdog time-out action Yes No 01 (hexadecimal)
13 Produced connection path length Yes No 00 (hexadecimal)
14 Produced connection path Yes No ---
15 Consumed connection path length Yes No 00 (hexadecimal)
16 Consumed connection path Yes No ---
17 Production inhibit time Yes No 00 (hexadecimal)
Item DeviceNet service Parameter option
Object instance 1 Service 05Reset No
0EGet_Attribute_Single No
10Set_Attribute_Single No
Item Section Information Max. number of instances
Object instance 2 Instance type Polled I/O 1
Production trigger Cyclic ---
Transport type Server ---
Transport class 2 ---

Table of Contents