169
Temperature Input Terminals Section 4-9
Dimensions
The following diagram shows the dimensions for the DRT1-TS04T and DRT1-
TS04P Temperature Input Terminals. All dimensions are in mm.
4-9-3 Mounting in Control Panels
Either of the following methods can be used to mount a Temperature Input
Terminal in a control panel.
Using Screws Open mounting holes in the control panel according to the dimensions pro-
vided for mounting holes in the dimensions diagrams and then secure the
Temperature Input Terminals with M4 screws. The appropriate tightening
torque is 0.6 to 0.98 N
m.
Using DIN Track Mount the back of the Temperature Input Terminal to a 35-mm DIN Track. To
mount the Terminal, pull down on the mounting hook on the back of the Termi-
nal with a screwdriver, insert the DIN Track on the back of the Terminal, and
then secure the Terminal to the DIN Track. When finished, secure all Slaves
on both ends of the DIN Track with End Plates.
(With connector installed)
Approx. 73
12
50 max.
150 max.
40 max.
Unit: mm
Mounting Hole Dimensions
Two, 4.2 dia. or M4
40±0.3
140±0.3