Environment-resistive Terminals (IP66) Section 5-3
does not exceed 2.4 A. If the total current exceeds 2.4 A, the power must
not be supplied from the connector; it must be supplied externally instead.
3. Wire colors in parentheses are the previous JIS colors for photoelectric
and proximity sensors.
Dimensions The following diagram shows the dimensions for the DRT1-MD16C and
DRT1-MD16C-1 Environment-resistive Terminals. All dimensions are in mm.
5-3-7 Mounting in Control Panels
Use screws to mount an Environment-resistive Terminal in a control panel.
These Terminals cannot be mounted on a DIN Track.
Attaching the Terminal from the Front
The Terminals are tapped with M5 threads, so use M4 screws to clear the
threads and attach the Terminal to the control panel from the front. Drill the
mounting holes in the control panel according to the dimensions shown in the
dimensions diagrams and secure the Terminal with M4 screws. The appropri-
ate tightening torque is 0.6 to 1.18 N
m.
Attaching the Terminal from the Rear
Drill the mounting holes in the control panel according to the dimensions
shown in the dimensions diagrams and secure the Terminal with M5 screws.
The appropriate tightening torque is 1.47 to 1.96 N
m.
Mounting Holes
Four, 4.2 dia. or M4
Four, 5.4 dia.
Four, M5
When screw mounting
from the front
When screw mounting
from the rear
Mounting screw
Nut
Mounting
screw