156
Analog I/O Terminals Section 4-8
4-8-4 Mounting in Control Panels
Either of the following methods can be used to mount an Analog I/O Terminal
in a control panel.
Using Screws Open mounting holes in the control panel according to the dimensions pro-
vided for mounting holes in the dimensions diagrams and then secure the
Analog I/O Terminal with M4 screws. The appropriate tightening torque is 0.6
to 0.98 N
⋅m.
Using DIN Track Mount the back of the Analog I/O Terminal to a 35-mm DIN Track. To mount
the Terminal, pull down on the mounting hook on the back of the Terminal with
a screwdriver, insert the DIN Track on the back of the Terminal, and then
secure the Terminal to the DIN Track. When finished, secure all Slaves on
both ends of the DIN Track with End Plates.
Connecting End Plates
Hook the bottom of the End Plate onto the DIN Track, as shown at (1) in the
following diagram, then hook the top of the End Plate as shown at (2).
Note Always attach End Plate to both ends of Slaves connected to DIN Track.
Mounting Direction Unless specific restrictions are given for the Slave, it can be mounted in any
direction. Any of the following directions are okay.
4-8-5 Wiring Internal Power Supplies and I/O Lines
The internal circuit power supplies and I/O lines are all wired to M3 screw ter-
minals. Connect M3 crimp terminals and then connect them to the terminal
block. Tighten the screws fixing the crimp terminals to a torque of 0.3 to
0.5 N
⋅m.
1
2
End Plate
ANALOG TERMINAL
IN
No.
NSMS
1 230
DRT1-AD04
ANALOG TERMINAL
IN
No.
NSMS
1 230
DRT1-AD04
ANALOG TERMINAL
IN
No.
NSMS
1 230
DRT1-AD04
ANALOG TERMINAL
IN
No.
NSMS
1 230
DRT1-AD04
Vertical
6.0 mm max. 6.0 mm max.