155
Analog I/O Terminals Section 4-8
The following table shows the lower and upper limits of the output ranges for
each output signal range setting.
Converted Data Output the converted data to the Master as shown in the following diagram.
The sign bit is turned ON to indicate that the converted value is negative, at
which time the converted value will be an absolute value.
Dimensions
The following diagram shows the dimensions for the DRT1-DA02 Analog Out-
put Unit. All dimensions are in mm.
Output signal range “Low” “High”
–10 to 10 V –11 V 11 V
0 to 10 V –0.5 V 10.5 V
1 to 5 V 0.8 V 5.2 V
0 to 20 mA 0 mA 21 mA
4 to 20 mA 3.2 mA 20.8 mA
Bit
First word
First word + 1
Sign
bit
Sign
bit
Output 0 converted data
Output 1 converted data
Two, 4.2 dia. or M4
150 max. 40 max.
Approx. 73
12
Mounting holes
40 0.3
±
140 0.3
±
(With connector attached)
Unit: mm
50 max.