286
RS-232C Units Section 6-2
Connecting End Plates
Hook the bottom of the End Plate onto the DIN Track, as shown at (1) in the
following diagram, then hook the top of the End Plate as shown at (2).
Note Always attach End Plate to both ends of Slaves connected to DIN Track.
Mounting Direction Unless specific restrictions are given for the Slave, it can be mounted in any
direction. Any of the following directions are okay.
6-2-11 Wiring
Internal Power Supply The recommended Power Supply Units are as follows:
• S82K-05024 (OMRON) or equivalent.
•S82J-@524 (OMRON) or equivalent.
Note 1. Always use crimp terminals for wiring.
2. Do not connect wires directly to the terminals.
3. Tighten terminal screws to a torque of 0.3 to 0.5 N • m.
4. Use the following M3 crimp terminals.
1
2
End Plate
DRT1-232C2
RS232C UNIT
MS
ERR
NS
RD1 SD1 RD2 SD2
No.
PORT1 PORT2
DRT1-232C2
RS232C UNIT
MS
ERR
NS
RD1 SD1 RD2 SD2
No.
PORT1 PORT2
DRT1-232C2
RS232C UNIT
MS
ERR
NS
RD1 SD1 RD2 SD2
No.
PORT1 PORT2
DRT1-232C2
RS232C UNIT
MS
ERR
NS
RD1 SD1 RD2 SD2
No.
PORT1 PORT2
Vertical
Internal power supply
+
–
Source
24 V DC
+–
6.0 mm max. 6.0 mm max.