Waterproof Terminals (IP67) Section 5-4
Wiring The following diagram shows the wiring of the DRT1-OD08CL Waterproof
Terminal (NPN).
The following diagram shows the wiring of the DRT1-OD08CL-1 Waterproof
Terminal (PNP).
Note External power supply line 0V and output line G are connected internally, as
are external power supply line 24V and output line V. When output power is
supplied to external power supply connectors, power can be supplied to out-
put devices from output lines G and V provided that the total current does not
exceed 2.4 A. If the total current exceeds 2.4 A, the power must not be sup-
plied from the connector; it must be supplied externally instead.